Fuse switch disconnect are suitable for AC 50Hz, rated voltage up to 660V, and DC voltage up to 440V. They are low-voltage power distribution components integrating isolation, switching, and short-circuit protection functions. The fuse is installed in the knife arm position of the moving contact of the disconnecting switch, or a combination of disconnecting switch and fuse connected in series is installed. The fuse interrupts short-circuit current, thus providing short-circuit breaking capability.
Technical Parameters
GRGLR-400/4F
- GR: Company code
- GLR: Fused disconnect
- 400: Rated current
- 4: 4 phrase
- F: Front operation
Product features
The fuse switch disconnect assembly has a modular structure, featuring a glass fiber reinforced unsaturated polyester resin shell, spring energy storage, and a bevel gear transmission acceleration mechanism for rapid connection and disconnection.
The fuse element is connected in series in a four-break multi-contact structure, automatically determining the limit positions of the on/off states and providing clear contact status indication.
Technical parameters
|
Code |
GRGLR-400 |
||
|
Conventional heating current (A) |
400 |
||
|
Rated insulation voltage (V) |
800 |
||
|
Rated impulse withstand voltage (kV) |
8 |
||
|
Rated working current (A) |
380V |
400 |
|
|
660V |
315 |
||
|
Rated making and breaking capacity (A) 1.05Ue |
AC660V,AC-23B |
Connect |
4000 |
|
COSΦ:0.35 |
|||
|
AC660V,AC-23B |
Disconnect |
3200 |
|
|
COSΦ:0.35 |
|||
|
Mechanical life (times) |
800 |
||
|
Electrical life (times) |
200 |
||
|
Operating force (N) |
30 |
||
|
Rated short-circuit current (kA) |
50 |
||
|
Pollution degree |
3 |
||
Dimension:


Operating methods
Direct side operation: Handle is installed on the right side of the switch;
Direct front operation: Handle is installed on the front of the switch;
External side operation: Handle is installed on the right side outside the distribution cabinet;
External front operation: Handle is installed on the front outside the distribution cabinet door.
Routine Maintenance
Visual Inspection
Check the casing for cracks and burn marks; ensure the transparent cover is free of dust and condensation.
The "Open (O) - Close (I)" markings on the operating handle should be clear, without looseness or discoloration.
Electrical Connection Check
Use an infrared thermometer to check the temperature of the wiring terminals. During normal operation, the temperature should be ≤ ambient temperature + 40℃, with no overheating (terminal discoloration, insulation aging).
Manually and gently shake the copper busbar/cable to confirm it is secure (if there is abnormal noise, retighten it).
Contacts and Fuses
After disconnecting the power annually, inspect the contact surface: if there is slight burning, smooth it with fine sandpaper; if the contacts are welded or deformed, replace the switch body. If a fuse blows, replace it with the same model (NT2).
Operating Mechanism
Apply a small amount of lubricant (such as silicone grease) to the handle rotation shaft every six months to ensure smooth operation. Verify the interlocking function: After closing the switch, try to open the cabinet door; confirm that it cannot be opened; when the cabinet door is open, the switch cannot be closed.
Applications of Disconnectors
In low-voltage power distribution systems, the main function of disconnectors is for inspection and maintenance safety.
1. Incoming lines at distribution boxes and panels
2. Incoming lines at the main circuit of motor control centers
3. Feeders leading out from low-voltage distribution cabinets in substations; when fuses are used as protective electrical devices, disconnector switch-fuse groups should be installed.
4. Data centers and similar locations
5. Isolation requirements for special locations
Isolation requirements for solar photovoltaic power supply devices
FAQ:
Q: Are you a trader or manufacturer ?
A: We are a manufacturer, welcome your visit to our factories.
Q: How can I get the sample?
A: Ship by air or express or sea according to your demands.
Q: How long does it usually produce?
A: Samples within 2 days, if purchase in bulk,it relies on the quantity.
Q: Can you install fuse for me ?
A:Yes, of course, please inform us before quoting.
Hot Tags: fuse switch disconnect, China fuse switch disconnect manufacturers, suppliers, factory