Load Break Isolator

Load Break Isolator

Details
The GRGL series load disconnect switches are suitable for AC 50Hz, rated voltage up to 660V, and DC rated voltage up to 440V, with a rated current range of 125A-1600A.
Category
Indoor Disconnect Switch
Share to
Send Inquiry
Description
Technical Parameters

 

product-600-437
product-600-438

The GRGL series load disconnect switches are suitable for AC 50Hz, rated voltage up to 660V, and DC rated voltage up to 440V, with a rated current range of 125A-1600A. These load disconnect switches feature a glass fiber reinforced unsaturated polyester housing. A spring-loaded acceleration mechanism enables rapid connection and disconnection. Two parallel double-break contact surfaces are used, with a leaf spring ensuring contact pressure. The switches automatically determine the extreme on/off positions and have clear on/off markings to indicate the position.

 

Technical Parameters

 

Model Specification

GRGL-1000

Agreed Heating Current (A)

1000

Rated Operating Current (A)

1000

Rated Insulation Voltage (V)

800

Rated Impulse Withstand Voltage (kV)

12

Rated Making Capacity (A)

10000

Rated Breaking Capacity (A)

8000

Mechanical life (times)

2500

Electrical life (times)

500

Short-time withstand current (kA/1s)

30

Operating force (N)

≤600

Pollution degree

3

Enclosure protection grade

IP00

 

Dimension

 

product-908-466

product-1002-396

Environmental Condition:

 

The switch shall operate reliably under the following conditions:

Altitude not exceeding 2000 meters;

Ambient temperature not exceeding +40℃ and not falling below -5℃;

Relative humidity not exceeding 95%;

No explosive atmosphere, and the atmosphere shall be free of gases and dust that could corrode metals or damage insulation;

No significant shaking or impact vibration;

No rain or snow intrusion.

 

Usage and maintenance:

 

 The switch should be installed vertically. Before installation, check that the nameplate information meets the usage requirements. Confirm that the switch is in the off position. Move the switch operating handle; if the arrow on the handle points to "0" and the observation window also displays "0", the switch is in the off position. If the arrow points to "|" and the observation window also displays "|", the switch is in the closed position.

 

 The terminals and bare busbars on the switch should be wrapped with insulation to prevent short circuits between phases.

 

  If the extended shaft of the externally operated switch is different from the handle hole, do not move the extended shaft to avoid damaging internal parts. Always adjust the switch position to make it coaxial.

 

 The switch should be maintained approximately every six months. If rotating parts are not flexible, apply MP-3 grease. Check for loose fasteners. Repair as needed; if damage is severe, stop using the switch.

 

OUR SERVICE

 

 Professional QC team to ensure your product better.

 Check the raw material before starting production.

 Random inspection during the processing.

 100% inspection before the shipment.

 

FAQ

 

Q: Can it be operated from outside the cabinet, or is it only possible to operate it by opening the cabinet door directly?

A: Yes, we have type of outdoor operation, an external control handle, please inform us before quote.

Q: Can you provide the disconnect switch cabinet and install it for me?

A: Yes, we have an electrical enclosure factory and can provide installation services.

Q: Could you put my own logo in the products ?

A: Yes, please send your logo design to us, and inform us before quoting.

Q: Does it come with installation parts?

A: Yes, we offer.

 

 