Low-voltage complete switchgear is a large-scale and widely used complete set of electrical products. It is widely used in low-voltage distribution systems of power plants, substations, industrial and mining enterprises and various types of power users. It plays the role of power conversion, distribution, control, protection and monitoring for power, lighting, distribution and motor control center, reactive power compensation, etc.
Low-voltage switchgear can be divided into the following categories: (According to the structural characteristics and use)
(1) Fixed panel switchgear
Fixed panel switchgear is often called switchboard or distribution panel. It is an open switchgear with a panel. The front has a protective function, and the back and sides can still touch the live parts. The protection level is low and it can only be used in industrial and mining enterprise substations with low requirements for power supply continuity and reliability.
(2) Enclosed switchgear
A closed switchgear refers to a low-voltage switchgear with all sides enclosed except the installation surface. The electrical components such as switches, protection and monitoring control of this switchgear are installed in a closed shell made of steel or insulating material, which can be installed against the wall or away from the wall. Each circuit in the cabinet may not be soundproofed, or may be isolated by grounded metal plates or insulating plates.
(3) Withdrawable switchgear
This type of switchgear uses a closed housing made of steel plates. The electrical components of the incoming and outgoing circuits are installed in withdrawable drawers, forming a functional unit that can complete a certain type of power supply task. The functional unit and the busbar or cable are separated by a partition made of grounded metal plates or plastic, forming three areas: busbar, functional unit and cable. There are also isolation measures between each functional unit. Withdrawable switchgear has high reliability, safety and interchangeability. They are suitable for use as a centralized control distribution center in low-voltage power supply and distribution systems with high power supply reliability requirements.
(4) Power and lighting distribution control boxes
Power and lighting distribution control boxes are mostly closed and vertically installed. Due to different usage scenarios, the protection level of the housing is also different. They are mainly used as distribution devices at power consumption sites.
The main technical parameters of low-voltage switchgear are as follows:
- Rated voltage, including the rated voltage of the main circuit and auxiliary circuit. The rated voltage of the main circuit is divided into rated working voltage and rated insulation voltage. The rated working voltage indicates the highest voltage of the power grid where the switchgear is located; the rated insulation voltage refers to the standard voltage value used to measure the insulation strength, electrical spacing and creepage distance of different potential parts of electrical appliances and their components under specified conditions.
- Rated frequency, generally 50Hz. For export products, the power supply frequency of some countries is 60Hz.
- Rated current, divided into two types, one is the horizontal bus rated current, which refers to the working current of the receiving bus in the low-voltage switchgear, the minimum is several hundred amperes, and the maximum can reach 5~7KA; the other is the vertical bus rated current, which refers to the working current of the branch bus (i.e., feeder bus) in the low-voltage switchgear, which is smaller than the horizontal bus current. The rated current of the drawer unit is generally smaller, and the larger ones are 400A, 630A, etc.
- Rated short-circuit breaking current, which refers to the ability of the switching device in the low-voltage switchgear to break the short-circuit current, depends on the switching device equipped with the low-voltage switchgear.
- Rated peak withstand current and rated short-time withstand current of the busbar, which indicate the dynamic and thermal stability of the busbar.
- Protection level, which refers to the ability of the housing to prevent solid foreign objects from entering the housing and contacting live parts or moving parts, and to prevent water from entering the housing. Generally, it should reach IP30, and higher requirements include P43, IP54, etc.
| Item | Data | |
| Rated Voltage /V | Main circuit | 380(660) |
| Auxiliary circuit | AC220,AC380,DC110,DC220 | |
| Rated insulation voltage /V | 690(1000) | |
| Rated frequency /Hz | 50 | |
| Rated current /A | Horizontal busbar | ≤4000 |
| Vertical busbar | 1000 | |
| Busbar rated short-time withstand current (1s)/kA | 50,80 | |
| Busbar rated peak withstand current (0.1s)/kA | 105,176 | |
| Protection level |
IP30,IP40 |
|