A disconnect switch is a switching device primarily used for isolating power sources, switching operations, and connecting and disconnecting low-current circuits. It lacks arc extinguishing functionality. When in the open position, the contacts have a specified insulation distance and a clear disconnection mark. When in the closed position, the isolating switch can carry the current under normal circuit conditions and the current under abnormal conditions (such as a short circuit) for a specified time. It is generally used as a high-voltage isolating switch, with a rated voltage of 1 kV or above. Its operating principle and structure are relatively simple, but due to its high usage and high reliability requirements, it has a significant impact on the design, construction, and safe operation of substations and power plants.
Basic Requirements for Isolators
1. Isolators should have a clear disconnection point to facilitate maintenance personnel in identifying whether electrical equipment is disconnected from the power supply.
2. Sufficient insulation distances should be maintained between disconnection points to prevent breakdown and endangerment to personnel in the event of overvoltage or interphase arcing.
3. They should have sufficient short-circuit stability and should not automatically disconnect due to electromotive force, which could cause a serious accident.
4. They should have a simple structure and reliable operation.
5. The main isolator and grounding isolator should be interlocked to ensure the disconnector is opened before the grounding switch is closed, or the grounding switch is opened before the disconnector is closed.
Structure and Corresponding Functions
Conductive Part
Generally composed of a moving contact and a stationary contact. In the closed state, they can stably and reliably pass the rated current, short-time withstand current, and peak withstand current; they can switch small capacitive and inductive currents or busbar transfer currents during opening and closing; and they should provide a safe and visible insulation break in the open state.

Insulators
Generally made of porcelain or silicone rubber. It supports the conductive parts and ensures reliable insulation between the conductive circuit and the ground, between the poles, and between the disconnects. It can reliably withstand the weight of the disconnector closing and opening units and the tension of the connected conductors; as well as the electromotive force generated by fault currents, wind forces, and vibrations caused by earthquakes. Some or all of the insulators also serve as the transmission component.

base
The base and transmission component, which primarily consists of the base frame and its attached transmission and conversion structures, has the following main functions: ensuring the structural characteristics of the product and withstanding all structural forces; providing an interface to the equipment installation foundation and attaching the grounding switch and interlocking device; transmitting ground operating instructions and operating energy to the main conductive parts, enabling them to accurately operate accordingly.

operating mechanism
The operating mechanism, which is divided into manual and electric operating mechanisms, specifically functions to accurately execute operating instructions, convert instructions into corresponding operating energy, convert manual force or motor rotation into the required rotation of the mechanism output shaft, and transmit this to the conductive parts through the operating transmission component to perform the corresponding opening and closing functions.

Correct Operation Sequence for Isolators
1. When operating an isolator, first check that the circuit breaker for the corresponding circuit is in the open position to prevent opening and closing the isolator under load.
2. When shutting down and energizing a line, the isolators must be opened and closed in sequence. When operating during a power outage, the circuit breaker must be opened first, followed by the line-side isolator, and finally the busbar-side isolator. The order for operating during power outages is the opposite of the order for shutting down. This is because in the event of an erroneous operation, following this sequence can minimize the scope of the accident and prevent it from spreading to the busbar.
3. During operation, if any serious defects such as severe damage to the insulator or the isolator's transmission rod are detected, operation must not be resumed.
4. When operating an isolator, an on-duty personnel should be on-site to check each phase's open and closed position, synchronization, contact depth, and other parameters to ensure correct operation and positioning of the isolator.
5. Isolators should generally be operated in the main control room. If the remote electrical control fails, manual or electric operation may be performed on-site, but this must be done with the permission of the station manager or technical supervisor and under on-site supervision.
6. Electrical, electromagnetic, and mechanical locking devices are installed between the disconnector, earthing switch, and circuit breaker to prevent accidental operation. Switching operations must be performed in sequence. If the locking device fails or the disconnector or earthing switch fails to operate properly, the position of the corresponding circuit breaker and earthing switch must be strictly checked according to the locking requirements.
Only after verification can the lock be released and operation resumed.
Note: Closing the disconnector must be done quickly and decisively, but avoid excessive force at the end of closing to prevent a shock. After the operation is completed, check that the disconnector is fully closed. After closing, ensure that the earthing switch is fully engaged with the fixed contacts and check the contact tightness. Opening the disconnector should be done slowly and cautiously, and then quickly as the blades leave the fixed contacts. Especially when cutting off the no-load current of the transformer, the charging current of the overhead lines and cables, the small load current of the overhead lines, and cutting off the loop current, the knife switch should be pulled quickly and decisively so that the arc can be extinguished quickly. After the switch operation is completed, check that each phase of the knife switch is indeed in the disconnected position, and the blade should be pulled as far as possible.