During the use of high-voltage disconnectors, whether they should be overhauled should be determined based on factors such as the condition of the equipment and the operating time. Minor repairs: These should generally be carried out in conjunction with preventive testing of the equipment, and the cycle should generally not exceed three years. For disconnector equipment that has not undergone condition-based maintenance but has undergone comprehensive modifications and meets the requirements of the "Technical Standards for AC High-Voltage Disconnectors", it is recommended that they be overhauled every 8 to 10 years. Temporary maintenance: Critical defects and serious defects discovered during operation should be repaired in a timely manner. How to deal with the following problems:
Isolator Connector Overheating
If the isolator contacts or terminal block are found to be overheating, efforts should be made to reduce or transfer the load, strengthen monitoring, and request a power outage for maintenance if necessary.
The main treatment methods are:
1) Contact Overheating: Generally, the static contact spring clip and burned contact fingers should be replaced, the oxide layer on the moving and static contacts should be removed, the moving and static contacts should be cleaned, Vaseline should be applied, and the bolts should be tightened. A complete solution is to replace the contacts.
2) Terminal Block Overheating: Check for hot spots, clean the contact surfaces, polish them, apply conductive paste, and tighten the bolts.
It is recommended to measure the circuit resistance before and after the overheating treatment to quantify the treatment effect.
Transmission Mechanism Failure
If the disconnector fails to operate electrically, first check for any operational errors. Then, check the operating and power supply circuits for integrity, and check whether the fuses are blown or loose. Check whether the electrical interlock circuit is functioning properly.
Isolator contact deformation due to welding, insulator damage, or severe electrical discharge
In these cases, immediately shut down the power supply and strengthen monitoring before shutting down.
Isolator Failure to Close
Failure to close the disconnector is often caused by corrosion, sticking, or improper adjustment during maintenance. In such cases, open the disconnector and then close it again. A power outage should be requested if necessary.
Disconnector refuses to open or close
(1) Due to mechanical failures such as the shaft pin falling off, the wedge bolt withdrawing, the cast iron breaking, or due to electrical circuit failure, the cutter bar and the operating mechanism may become disconnected, causing the disconnector to refuse to close. In this case, an insulating rod should be used for operation, or a wrench should be used to turn the shaft of each phase disconnector while ensuring personal safety.
(2) Refusal to open: When the disconnector cannot be opened, if the operating mechanism is frozen, it can be gently shaken and the supporting porcelain bottle and various parts of the mechanism can be observed to find the location of the obstruction based on where deformation and displacement occur. If the obstruction occurs in the contact part of the disconnector, it should not be opened forcibly, otherwise the supporting porcelain bottle may be damaged and cause a serious accident. In this case, the only way to deal with it is to change the operating mode of the equipment.
After troubleshooting, the following tests should be carried out, which should all comply with the manufacturer's technical requirements: contact insertion depth when the disconnector main knife is closed, contact insertion depth when the earthing knife is closed, check whether the knife is in the over-dead point position when it is closed, manually operate the main knife and the earthing knife to close, 5 times each, electrically operate the main knife and the earthing knife to close, 5 times each, measure the contact resistance of the main knife and the earthing knife, check the mechanical interlock and the three-phase synchronization.